MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 5 Parameters MICROMASTER 440 This Parameter List must only be used together with the Operating Instructions or the Reference Manual of the MICROMASTER 440. Please pay special attention to the Warnings, Cautions, Notices and Notes contained in these manuals. Table of Contents. Prolong the service life of your MICROMASTER 440 Inverter and the equipment you connect to it. WARNING This equipment contains dangerous voltages and controls potentially dangerous rotating mechanical parts. Non-compliance with Warnings or failure to follow the instructions contained in this manual can result in loss of life, severe. MICROMASTER 420 Documentation Getting Started Guide Is for quick commissioning with SDP and BOP. Operating Instructions Gives information about features of the MICROMASTER 420, Installation, Commissioning, Control modes, System Parameter structure, Troubleshooting, Specifications and available options of the MICROMASTER 420. Parameter List. MICROMASTER 440 Parameter List 4 6SE6400-5BB00-0BP0 Warning Please refer to all Definitiones and Warnings contained in the Operating Instructions. You will find the Operating Instructions on the Docu CD delivered with your inverter. If the CD is lost, it can be ordered via your local Siemens department under the Order No.
Safety and will also help prolong the service life of your MICROMASTER 430 Inverter and the equipment you connect to it. General WARNING ¾ This equipment contains dangerous voltages and controls potentially dangerous rotating mechanical parts. Siemens AG MICROMASTER 430. Siemens handbooks are printed on chlorine-free paper that has been produced from managed sustainable forests. No solvents have been used in the printing. Safety and will also help prolong the service life of your MICROMASTER 420 Inverter and the equipment you connect to it. General WARNING.
6 Commissioning
Issue 10/06
MICROMASTER 440
28
Operating Instructions (Compact)
6 Commissioning
6.1 Quick
commissioning
The frequency inverter is adapted to the motor using the quick commissioning
function and important technological parameters are set. The quick commissioning
shouldn't be carried-out if the rated motor data saved in the frequency inverter
(4-pole 1LA Siemens motor, star circuit configuration frequency inverter (FU)-
specific) match the rating plate data.
Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.
Factory
setting
P0003 = 3
User access level *
1 Standard:Allows access into most frequently used parameters
2 Extended: Allows extended access e.g. to inverter I/O functions
3 Expert (For expert use only)
Parameter filter
*
0 All parameters
2 Inverter
3 Motor
4 Speed sensor
P0010 = 1
Commissioning parameter *
0 Ready
1 Quick commissioning
30 Factory
setting
NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.
P0100 =...
Europe/ North America
(enters the line supply frequency)
0 Europe [kW], frequency default 50 Hz
1 North America [hp], frequency default60 Hz
2 North America [kW], frequency default60 Hz
NOTE
For P0100 = 0 or 1, the setting of switch
DIP50/60
determines the value of
P0100.
OFF =
kW, 50 Hz
ON =
hp, 60 Hz
Inverter application
(enters the required torque)
0 Constant torque (e.g. compressors, processing machines)
1 Variable torque (e.g. pumps, fans)
NOTE
This parameter is only effective for drive inverters
≥ 5.5 kW / 400 V
Select motor type
1 Asynchronous motor (induction motor)
2 Synchronous motor
NOTE
For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are
permitted.
P010
0 =
1, 2
P010
0 =
0
Siemens Micromaster Manual
START
P0004 = 0
0
Siemens Micromaster 440 Wiring
1
0
Siemens Inverter Micromaster 440 Manual

P0300 =... P0300 =...
Siemens Micromaster 440 Faults
P0205 =... P0205 =...
1
0
0